 EARTH CLAMP TESTER_KEW 4202
EARTH CLAMP TESTER_KEW 4202
  • Real time measurements can be transferred, shown and saved on Android device (up to 100 measurements)
  • Saved data includes measurement, GPS location and date & time; Easy to check on map "When" and "Where" the measurement was made
  • Comparator function on Android device informs when the measured value is lower/higher than the preset value
Earth /Ground resistance and Leakage current measurement functions
  • The earth resistance from 0.05 to 1200 Ω can be measured without the auxiliary earth spikes in multi-earthing systems
  • True RMS leakage or phase current readings from 0.1mA to 30.0A provides vital additional information in earthing networks
  • Filter function offers increased immunity to electrical noise and a Noise mark appears in excessively high noisy environments
Giá: vui lòng liên hệ
  • Thông tin chi tiết

  •  
    Function
    Range
    Resolution
    Measuring Range
    Accuracy
    Earth resistance
    Auto range
    20Ω
    0.01Ω (*)
    0.00~20.99Ω
    |±1.5%±0.05Ω
    200Ω
    0.1Ω
    16.0~99.9Ω
    |±2%±0.5Ω
    100.0~209.9Ω
    |±3%±2Ω
    1200Ω
    160~399Ω
    |±5%±5Ω
    400~599Ω
    |±10%±10Ω
    10Ω
    600~1260Ω
    ---
    AC current
    (50Hz/60Hz)
    Auto range
    100mA
    0.1mA
    0.0~104.9mA
    |±2%±0.7mA
    1000mA
    1mA
    80~1049mA
    |±2%
    10A
    0.01A
    0.80~10.49A
    30A
    0.1A
    8.0~31.5A
    Operating indication
    Earth resistance function:

    Constant voltage injection
    Current detection (Frequency: Approx. 2400Hz)
    Dual Integration

    AC current function: Successive approximation
    Over-range indication
    "OL" is displayed when input exceeds the upper limit of a measuring range
    Response time
    Approx. 7 seconds (Earth resistance)
    Approx. 2 seconds (AC current)
    Sample rate
    Approx. 1 time per second
    Power source
    LR6/R6 (AA) (1.5V) × 4
    Current consumption
    Approx. 90mA (max. 140mA)
    Measurement time
    Approx. 21 hours (when LR6 is used)
    Approx. 5 hours (when R6 is used)
    Auto power-off
    Turns power off about 10 minutes after the last button operation
    Applicable standards
    IEC 61010-1 CAT.IV 300V Pollution degree 2
    IEC 61010-2-032, IEC 61326-2-2 (EMC)
    Withstand voltage
    AC 5320Vrms/5 seconds
    Between the Transformer jaws fitted parts and case enclosure (except for jaws)
    Conductor size
    Approx. φ32mm
    Dimension
    246 (L)×120 (W)×54 (D) mm
    Weight
    Approx. 780g (including batteries)
    Accessories
    8304 (Resistors for operation check)
    9167 (Carrying case [Hard])
    LR6 (AA) × 4, Instruction manual

    • Crest factor < 3 (50Hz / 60Hz, peak value shall not exceed 60A)
    (*) 4 counts or less are corrected to 0.