Function | Range | Resolution | Measuring range | Accuracy | ||||
Earth resistance Auto range | 20Ω | 0.01Ω* | 0.00~20.99Ω | |±1.5%±0.05Ω | ||||
200Ω | 0.1Ω | 16.0~99.9Ω | |±2%±0.5Ω | |||||
100.0~209.9Ω | |±3%±2Ω | |||||||
1200Ω | 1Ω | 160~399Ω | |±5%±5Ω | |||||
400~599Ω | |±10%±10Ω | |||||||
10Ω | 600~1260Ω | --- | ||||||
AC current (50Hz / 60Hz) Auto range |
100mA | 0.1mA | 0.0~104.9mA | |±2%±0.7mA | ||||
1000mA | 1mA | 80~1049mA | |±2% | |||||
10A | 0.01A | 0.80~10.49A | ||||||
30A | 0.1A | 8.0~31.5A | ||||||
Operating system |
|
|||||||
Over-range indication | "OL" is displayed when input exceeds the upper limit of a measuring range | |||||||
Response time | Approx.7 seconds (Earth resistance) Approx.2 seconds (AC current) |
|||||||
Sample rate | Approx. 1 times per second | |||||||
Power source | DC6V : R6P (sizeAA manganese battery) × 4pcs, or LR6 (sizeAA alkaline battery) × 4pcs |
|||||||
Current consumption | Approx. 50mA (max. 100mA) | |||||||
Measurement time | Approx. 12 hours (when R6P is used) Approx. 24 hours (when LR6 is used) |
|||||||
Auto power-off | Turns power off about 10 minutes after the last button operation. | |||||||
Applicable standards | IEC 61010-1 : 2001 (CAT.IV 300V Pollution degree2) | |||||||
Withstand voltage | AC5320Vrms / 5 seconds Between the Transformer jaws fitted parts and Case enclosure (except for jaws) |
|||||||
Conductor size | Approx. 32mm max. | |||||||
Dimension | 246(L) × 120(W) × 54(D)mm | |||||||
Weight | Approx. 780g (including batteries) | |||||||
Accessories | Battery R6P : 4pcs Instruction manual : 1pc 8304 (Resister for operation check : 1pc) 9128 (Hard case : 1pc) |